|
|
 |
 |
Tecnical Information
 |
Static loading
PANELS
The permissible deflection is 1/300 of the length of a panel, i.e.
2mm for 600 x 600 mm panel.
Uniform distributed load:
This type of loading, which is still currently referred to, is not
representative of the mechanical performance of an access floor.
However, the admissible uniform distributed load is admitted to
be 5 times the measured centre of edge point load.
According to the types of panel and framework, the distributed load
varies from 10 000 to 30 000 N/m2.
Concentrated load:
It is applied by the way of a 25 x 25 mm indentor:
a) either at the centre of a panel.
b) or at the centre of one edge.
With very few exceptions, this type of loading is the most unfavorable.
Safety factor - failure load
The failure load applied on the weakest point of the panel must
be at least equal to 2.5 times the edge point load.
PEDESTALS
a) Concentrated load:
The pedestal is progressively loaded, by way of a 40 x 40 mm plate,
until it reaches the buckling point. See the graphs on Pedestal
page for permissible loads.
b) Eccentric load:
The 40 x 40 mm plate is moved out of centre in order to simulate
the edge of a panel.
The loading before buckling must be at least equal to twice the
edge point load.
Coverings
Wear and punching classification
The reports No. 1504 dated may, 1978 and No. 2183 dated September,
1987 have set up the UPEC classification for non-industrial applications.
In this document:
U = Wear
P = Punching
E = Waterproofness
C = Chemical
All these characteristics have rising indexes from 0 to 5 according
to the required degree of resistance.
The reports No. 1716 and 1717 dated July, 1981 concerning PVC coverings
and report No. 2288 dated October, 1988 concerning textile coverings
defined test methods to determine coverings' indexes for the above
U-P-E-C characteristics.
So, a U3P2E2C1 classified room, for example, can only be equipped
with a covering which has characteristc indexes identical or superior
to those of the room, in ou example U3 minimum, P2 minimum, E2 minimum,
C1 minimum.
Within the framework of the European regulations, UEATC (European
Union of Agrement) has published instructions for the agrement of
PVC floor coverings. These instructions appear in the CSTB report
No. 2182 dated September, 1984.
They recapitulate the classification of rooms and coverings. The
used characteristics are GW:
G = Wear + Punching (index 1 to 5)
W = Waterproofness
Tables enable the connection between G and U.P.
Please note that the UP or G classifications are available for a
covering bonded on a continuous and rigid surface and cannot be
valid for the same covering bonded on raised floors.
The vertical warpings due to tolerances of the panels' thickness
and deflections under loading can provoke partial deterioration
of trim edges when moving furniture or castor chairs.
|
 |
Electrical characteristics
A. ELECTROSTATIC PROPERTIES
The ability of a covering to accumulate electrostatic loads and
its ability to eliminate these loads quickly are essential for the
antistatic properties of an access floor. The measurement of the
transversal resistivity-Rt enables the estimation of the ability
to eliminate the electrostatic loads.
The used method has been set up by the Standard NFP 62-001 part
C issued from the Standard NFPA 99. The CEN-ELEC (European Committee
for Standardisation for Electricity) has set up Working groups in
order to harmonise the characteristics of classifications and the
measuring methods.
The following classifications and definitions can be used until
the development of future European Standards: Physiological antistatic:
Electrostatic charging potential < 2.5 KV and Rt < 1012
Ohms.
Dissipative: Rt between 5 x 105 and 108 ohms
Electrostatic conductive: Rt between 104 and 5 x 105
ohms - Discharge time < 1 second.
B. INSULATION PROPERTIES
For some applications, insulating access floors are required.
EQUIPONTENTIAL BONDING AND EARTHING
It has 2 purposes:
- To enable an easy electrostatic discharge. The purpose is easily
achieved.
- To ensure peoples security by linking the metallic parts that
constitute the access flooring. The second purpose is made difficult
by the lack of definition concerning the metallic earthing.
The equipotential bonding is automatically achieved by the contact
between the metallic parts of the framework and the metallic bottom
of the panels. The electrostatic conductive joints are obstacles
to an efficient equipotential bonding.
The equipotential bonding is completed by copper strap network connecting
some pedestals to each other. Finally, this network is connected
to the earthing by companies in charge with electricity.
|
 |
Fire protection.
The regulations for access flooring refer to:
- the reaction in front of fire.
- the partitioning of the plenum.
- the calorific potential.
They vary according to the use of the rooms and the classification
of the building inside which the access floors are installed.
REACTION IN FRONT OF FIRE
For the moment, there is no uniform classification method in Europe.
In France, the decree dated June 30th, 1983 defines 5 classes for
the materials: M0, M1, M2, M3, M4.
The test method used is the radiation test. The tested side is the
bottom of the panel. The classification of the superior part of
the panel is the same as for the covering.
PARTITIONING OF THE PLENUM
Plenum dividers made of M0 materials or fireproof partitions, with
a 1/4 hour flame protection, can be provided if required by regulation.
Every partitioned area has a maximum surface of 300m2
and a maximum length of 30 meters.
Acoustic insulation
Please note that acoustic insulation tests for access floors do
not exist in Europe and elsewhere. Studies concerning this subject
have been carried out by the TC 126 group with CEN (European Committee
for Standardization), since 1992. The results of the TC 126 works
and its applications by way of a CEN Standard will require several
years.
By that time, the figures provided by some manufacturers, and obtained
by way of different methods and indexes cannot be compared.
The testing method used for suspended ceilings, but reversed in
the case of raised floors, could be used as a basis for TC 126 studies.
In that case the acoustic insulation would be then measured between
2 adjacent rooms equipped with access floors and seperated by a
partition.
Under such conditions, our access floors can reach airborn sound
insulation values from 38 to 44 dbA, as stated on individual technical
sheets of our panels. The insulation to impact sound depends mainly
on the type of coverings bonded on the panels. The textile coverings
are most efficent.
Requirement for rooms to be installed with access flooring
Conditions:
- Not to be exposed to bad weather
- Rooms must be equipped with outside glazing
- Concrete slab and plaster walls must be dry.
- Not to be exposed to rehumidification risks.
- To get a concrete floor conform to article 5.2.2 of DTU 21:the
raw concrete is not allowed
- Not to be encumbered with materials or tools and get a dry
and clean concrete.
- Free of any other trades.
- All rooms adjacent to the access floor must have the same floor
height.
- The ambient temperature of the rooms where the access floor
is to be installed should be kept between 5oC and 24oC
and the relative humidity between 45% and 70%. If the temperature
is above 24oC (but never above 30oC) the
relative humidity should not be over 50%. The subfloor temperature
should not be below 5oC.
- No water or any other liquid should be spread under or on top
of the access floor.
Seismic zones
The decree No. 91.461 dated May, 14th 1991 defines the building
classes, and classifies the French regions in seismicity zones.
For normal risk buildings classified C and D and within the zones
II and III special steps must be taken, i.e:
- Every pedestal must be fixed to the concrete by way of adhesive
or mechanical process.
- In the case of plenum heights superior to 250 mm the pedestal
must lay on stringers which are mechanically fixed to the pedestals.
Access floor levelling
FINISHED HEIGHT:
An adjustment inferior or equal to 5 mm is possible compared to
the theorical finished height.
HORIZONTALITY:
Within a 5 m x 5 m area, the difference in horizontality must not
exceed 3 mm.
Within the total surface of the access floor, the difference must
not exceed 10 mm.
FLATNESS:
Along a 2 metre long profile, the level variation must not exceed
2 mm. The tolerances of manufacturing come in addition to this figure.
VERTICAL WARPING BETWEEN PANELS:
The vertical warping between the upper part of two adjacent panels
must not exceed 1mm. The panels peripheral edgings are not taken
into account.
Return to top^
|
|
 |